Module Blower Only Works Sometimes? Check the Drip Pan
Anderson Fleet Service · Kinsman, OH
Complaint on this one: the blower motor in the module only works sometimes.
Intermittent problems are the worst, because half the time you show up and everything works. Luckily, when I got to the station, the blower wasn’t working.
Step 1: Give it a poke
Opened up the HVAC box far enough to see what I call the cage fan. It looks like a hamster wheel on both sides of a motor, and it’s what blows air through the module.
Switched the blower on high, took my long screwdriver and gave the fan wheel a poke.
Instantly, full speed.
That tells me it’s probably a brushed motor, and the brushes are either dirty or worn out. On an old truck, I’d call that a worn-out motor and move on.
But this ambulance wasn’t very old. A motor shouldn’t be doing that this soon. So I dug deeper.
Step 2: Open the box up
Removed the HVAC box as far as I could and pulled the covers off.
The A/C drip pan was full of standing water.
That water is supposed to run out of the drip pan, down the drain lines, down the front wall and out onto the ground. It wasn’t going anywhere. It was just sitting in the box.
Meanwhile, that blower is moving a lot of air, fast. As it blew, it was pulling water up out of the drip pan and blowing humid air all through the ambulance.
And it was rusting out the blower motor.
Step 3: The real damage
Once I had the whole blower motor exposed, it was obvious. The entire thing was covered in rust. Rusted from the inside out.
That motor was less than a year old. All because of a plugged drip pan.
Step 4: Clear the drain
Ran my snake up the drip line and pulled out a bunch of wood shavings and debris. Probably left over from when they built the ambulance, and it finally worked its way down into the line.
When I was done, I dumped a full gallon of water into the drip pan. Ran right out.
Unfortunately, the blower motor still had to be replaced. But this time, it shouldn’t happen again.
Takeaways from the field
- Blower comes on when you poke the wheel? Likely brushes. But ask why.
- If the part failing is newer than it should be, something else is killing it. Find that, or you’ll be replacing it again.
- Check the A/C drip pan and drain lines any time you’re in the HVAC box. Standing water means a plug.
- A plugged drain doesn’t just leak. The blower picks that water up and blows it through the box and into everything.
- Pour water in the pan when you’re done. If it runs out, you’re good.
Final word
I could’ve swapped the motor and left. It would have worked for a while, then rusted out again. The motor was the symptom. The drain was the problem. If your module blower is acting up, give us a call.